Abstract

Detect fires in or near mine shafts, isolate smoke filled areas, and remotely extinguish fire. Approach A system (of sensors, automatic alarms, an aboveground control console, remotely operated ventilation doors, and sprinklers) has been built from off the-shelf components, and fire, tested in two mines. How It Works The system uses three different kinds of sensors that can detect the heat or smoke of a fire and automatically actuate alarms. When the alarm sounds in the control center on the surface, water sprays in the mine shaft and shaft station areas can be remotely turned on to deluge both the inside and the outside of the mine shaft's wooden support structure. To protect miners from toxic fumes, smoke control doors can be closed or opened, either remotely from the control center or directly by miners using the manual or electrical actuators at the door locations. Man doors built into each ventilation door allow persons to pass without opening the main door.