RI 8527 SF6 Tracer Gas Tests of Bagging-Machine Hood Enclosures

The National Institute for Occupational Safety and Health (NIOSH)
Robert P. Vinson
Organization:
The National Institute for Occupational Safety and Health (NIOSH)
Pages:
13
File Size:
3158 KB
Publication Date:
Jan 1, 1981

Abstract

This Bureau of Mines report presents the results of tracer gas studies conducted at three facilities where bagger hoods had been installed several years ago to remove airborne silica dust from the vicinity of the bagging operator. The studies indicated that for optimum benefits makeup air must be evenly dispersed, the hood enclosures and duct systems must be as airtight as possible, the average intake air velocity of each hood should be at least 200 fpm, and the hoods and duct systems must be properly maintained.
Citation

APA: Robert P. Vinson  (1981)  RI 8527 SF6 Tracer Gas Tests of Bagging-Machine Hood Enclosures

MLA: Robert P. Vinson RI 8527 SF6 Tracer Gas Tests of Bagging-Machine Hood Enclosures. The National Institute for Occupational Safety and Health (NIOSH), 1981.