RI 8658 Superheated Drop Vaporization: Halon 1301

- Organization:
- The National Institute for Occupational Safety and Health (NIOSH)
- Pages:
- 22
- File Size:
- 1135 KB
- Publication Date:
- Jan 1, 1982
Abstract
The Bureau of Mines has developed a time-dependent droplet vaporization model (in the absence of forced convection) that can be applied to the vaporization of liquid Halon 1301 droplets (vapor pressure at 300 K = 14 atm) sprayed from an extinguisher. It was found that rapid surface vaporization quickly lowers the droplets' surface temperature very near to the boiling temperature, and the vaporization becomes diffusion controlled. Although the lifetime of the droplet is proportional to the square of the initial radius of the droplet, the elapsed time prior to complete droplet vaporization is not proportional to the square of the droplet radius, as an equilibrium model would indicate.
Citation
APA:
(1982) RI 8658 Superheated Drop Vaporization: Halon 1301MLA: RI 8658 Superheated Drop Vaporization: Halon 1301. The National Institute for Occupational Safety and Health (NIOSH), 1982.