Road Tunnel Protection by Water Mist Systems û Implementation of Full-Scale Fire Test Results into a Real Project

- Organization:
- The Australasian Institute of Mining and Metallurgy
- Pages:
- 5
- File Size:
- 253 KB
- Publication Date:
- Jan 1, 2008
Abstract
Truck fires in a tunnel can create heat release rates (HRR) significantly higher than 100 MW. Because of a fast spread of smoke and heat the self-rescuing period is shortened significantly. Furthermore, it was experienced that firefighters are not able to approach the fire because of enormous heat and radiation. As consequence, the fire may spread to adjacent vehicles, which is reported for distances of more than 50 m. Tunnels can be damaged severely by fires and the repair works causes long closing time of tunnels. In addition to direct costs for the refurbishment of the tunnel, further economic losses will occur due to the closure time. Conventional deluge systems in Japanese and Australian road tunnels have been known since the 1960s. During the last years the research work was concentrated in the development of more effective and cost-effective solutions based on water mist technology. Orientating fire tests as well as specifications of minimum requirements were carried out within the European research project UPTUN. This basic work was extended by the safety of life in tunnels (SOLIT) research project, funded by the German government. The scope of SOLIT was not only to study the effects of water mist fire suppression systems in tunnels, but also the interactions with other safety systems, such as fire detection, passive fire protection or ventilation. Furthermore, the integration of active fire suppression systems into a holistic tunnel safety system was part of the work program. Within this research project a large-scale fire test program with more than 50 fire tests, including 25 truck fires with a potential HRR of almost 200 MW, was carried out in the test tunnel of San Pedro des Anes (Spain). Furthermore, a two-week testing and training period with the Madrid Fire Brigade was carried out after the SOLIT program. Two fundamental results were achieved during the fire tests:Primarily, water mist systems are able to control the HRR of fires in tunnels, so the atmosphere will be improved significantly. Hazardous effects of toxic smoke on people will be reduced and due to the reduction of temperatures and radiation, a firefighterÆs approach is improved significantly. Furthermore, the fire spread will be hampered and the thermal load on the building structure also be reduced. Secondarily, due to positive interactions with the ventilation system, the effectiveness of a tunnel ventilation system, longitudinal as well as semi-transversal, is increased significantly. Based on the results of the SOLIT research project, a water mist system was applied into several parts of the M30 tunnels in Madrid. As a basic principle the technical equipment and the methodology of implementation comply with the UPTUN 251 guidance, recommending minimum standards for water-based fire suppression systems in tunnels.
Citation
APA: (2008) Road Tunnel Protection by Water Mist Systems û Implementation of Full-Scale Fire Test Results into a Real Project
MLA: Road Tunnel Protection by Water Mist Systems û Implementation of Full-Scale Fire Test Results into a Real Project. The Australasian Institute of Mining and Metallurgy, 2008.